| Sign In | Join Free | My insurersguide.com |
|
Brand Name : HJ
Model Number : VF-1
Certification : Calibration Certificate(cost additional)
Place of Origin : China
MOQ : 1 set
Price : Negotiatable
Payment Terms : T/T,L/C
Supply Ability : 5 set per month
Delivery Time : 15 days
Packaging Details : Plywood
copper block : 9mm in diameter, 10 ± 0 .05g before drilling
temperature resistance : 1100°
Product name : Flammability Test Chamber
Standard : IEC 60332
Function : Single Cable Burning Test
Metallic screen : H1200mm*W300mm*D450mm
Fixed horizontal support of the sample : 2, distance:550mm
Gas : >95% propane or coal gas
Vertical Burning Test Apparatus for Single Wire & Cable | Flammability Testing Equipment for IEC & UL Compliance
Product introduction:
Vertical Burning Test Apparatus is a professional flammability testing solution designed for single insulated wires and cables. Manufactured by HongCe, a trusted original factory in China, this device helps engineers assess flame propagation, after-burning, and after-glow performance in accordance with global safety standards. Stable, precise, and easy to operate, it is widely used in laboratories, compliance departments, and cable manufacturers.
Application:
Cable and wire factories
Electrical accessory manufacturers
Household appliance industry
Automotive cable production
Aerospace and railway wiring materials
International Standards:
IEC 60332-1-1 / IEC 60332-1-2: Tests on electric and optical fibre cables under fire conditions — Part 1
UL 2556: Wire and Cable Test Methods
Technical Parameter:
| Working voltage | 220V/50Hz |
| Control operation mode | Electrical control, button operation |
| Blast burner standard | IEC60695-11-2 Annex A,Burner opening:Φ7±0.05mm,made of brass |
| Gas flow and gas category | Mixture gas:650±30mL/min propane;10±0.5L/min air,Dual flow meter adjustment |
| Burning time | 9999X0.1S |
| Burning angle | Tilt 45°±2°,Adjustable |
| Test flame calibration | Temperature measuring copper head:1000W:Ф9mm±0.01mm,weight before drilling:10 ± 0 .05g |
| Thermocouple: The American original Omega φ0.5 armour nickel-chromium/nickel aluminum wire K-Thermocouple,temperature resistance 1100° | |
| Distance between the bunsen burner port to temperature measuring copper block:95 mm | |
| Flame height:Inner flame:55±5mm,Outer flame:180±10mm | |
| Temperature rise time from 100±5°C to 700°±3°C 45±5s | |
| Metallic screen size | H1200mm*W300mm*D450mm |
| Combustion chamber | 1 m³ |
| Gas | >95% propane or coal gas |
| Test sample | Length:600±25㎜,distance from the bottom:50mm |
| Fixed horizontal support of the sample | 2, distance:550mm |
Test Objects
Single insulated wires
Small-size cables
Optical fiber cables
PVC/XLPE insulated conductors
Low-smoke zero-halogen (LSZH) cables
Test Capabilities
Flame propagation measurement
After-flame time
After-glow time
Dripping performance
Material carbonization length
Ignition resistance
Combustion behavior analysis
Detailed images:

|
|
Vertical Burning Test Apparatus with 1100° Temperature Resistance and 9mm Copper Block for IEC 60332 Compliance Images |